DSP-SS1-AR Motor Protection Relay/2CT Based,Auto Reset
Motor Protection Relay/2CT Based,Auto Reset
Main Feature
■ MCU based digital control : optimized protection
■ Compact size, Practical simple application
   •Protection : - Over current / Under current, Phase Loss, Locked rotor
                        - Protection for Phase loss and Locked rotor is executed based on over current
   •Possible to check actual current and trip state based on LED indication
■ 3 phase load protection through 2 CT
■ To cover wide and precise current range for the protection
   •10 Type : - Definite T-I : 0.3A∼12A(0.3~6A for external CT)
                    - Matched with external CT : 1~600A, secondary rating of external CT is 5A
   •60 Type : Definite T-I : 2A∼60A
■ LED Indication
        DIV                                                         LED Indication                                      Description
Control Power                                                POWER/RUN                                 Green LED is turned on
Motor operation                                             POWER/RUN                                     Red LED is turned on 
Over / Under current protection                     POWER/RUN           Red LED is flickered with 1sec interval during o-time
                                                                               TRIP                                        Yellow LED is turned on

                                                                 Trip Cause Indication
Cause                                                    POWER(Green)/RUN(Red)
Phase Loss                        
L1 Red LED is turned on continuously by the pattern with 1sec(on)-1sec(off)-1sec(on)
L2 Red LED is turned on continuously by the pattern with 1sec(on)-0.5sec(off)-0.5sec(on)
L3 Red LED is turned on continuously by the pattern with 1sec(on)-0.5sec(off)-0.5sec(on)-0.5sec(off)-0.5sec(on)
Locked Rotor                    Trip Yellow LED is flickered by the pattern with 1sec(on)-1sec(off)-1sec(on)

■ Convenient functional selection by DIP SW
   •N type : trip output(95-96,97-98) is energized in case control power is loaded
   •R type : trip output(95-96,97-98) is not energized in case control power is loaded
                 - trip output is not responsed for selection of DIP SW in case normal operation is processed
   •RP ON : able state to protect reverse phase protection      •RP OFF : disable state to protect reverse phase protection
■ Reset after tripped
   •Manual : press “RESET” SW after prestting "OFF" for R-Time knob    •Automatic : after R-Time
   •Electrical : control power(A1-A2) off
                → possible to make remote control by power switch with remote distance
■ Self-diagnostic function : “TEST” SW