DSP-VIP-5EM DSP-VIP-5-Series(5EM/5EL,5TM/5TL,5CM/5CL,5SM)
DSP-VIP-5-Series(5EM/5EL,5TM/5TL,5CM/5CL,5SM)
Main Feature
  • Panel Flush Mounting Type
  • Access restricted to authorized operator : Password
  • To response for various motor starting system and to use trip for the protection : the application for trip output according to Logic input as follows : applied mode is "out/LooFF/a/b"
    • Trip output : C1-M, 97-98/Main trip, 07-08/Aux
    • As the control power is powered :
      • for selecting LooFF(“Auto" is displayed in the initial state)
        • disable for logic input
        • C1-M:open⇢close in motor start/(open in trip)
        • sequence for contactor ON-OFF ⇢ C1-M(b),97-98(a)/actually just like 1b-1a
      • for selecting one of a / b("LOP", rcs. EFI are displayed in the initial state according to logic input state)
        • C1-M:open ⇢ close in motor start
        • sequence wiring for contator ON-OFF⇢C1-M(1b)
  • Protection : Over current/Under current/Phase loss/Reverse phase/Locked rotor/Shock(Stall)/Ground fault,[Short circuit:5SM Type]
  • Indication :Current(each phase line or average),earth current, load factor,accumulated working time[AWT]
  • To cover a wide and precised current range for the protection
    • 03 Type :0.2 ∼ 6A - only available for 5SM Type
    • 70 Type : 0.2A∼70A --changed naturally into 0.2~6A with external CT if 5A is preset in cto mode or for 5SM type
    • Extended current range with external CT : 1A∼3000A
  • To keep a steady characteristics in the noisy installed environment : embedded RMS chip/correct RMS current value
  • The classification for Logic Input :LOP>> rcs >> EFI(External Fault Input)/LOP:#1,#2, rCS:#4,#6:EFI
  • To realize instant trip time for the ground fault protection :0.1∼30sec/Definite , 0.05sec/instant
  • To realize instant trip time for the short circuit protection : 0.08 sec/instant T-I for 5SM Type
  • "Shock" protection :availble for instant mechanical shock due to over load while crasher,roller,conveyer,etc are working
  • To indicate a necessasary information in every 3 sec
  • Convenient installation of ZCT to sense a zero phase current for GF protection
    • Standard type : to use external ZCT(200mA/1.5mA)
    • Optional type : embedded ZCT(not available for external CT application)
  • High sensitive level and wide range for ground fault protection : 30mA ∼ 4A
  • Main contactor auto close : in case a line power is "ON" again withinin a preset time(SDDT) after a line power is "OFF" during normal operation, main contactor is closed orderly according to another preset time(DOMT)
  • Various way to reset after trip: Manual,Electrical or Automatic /to response flexibly for applied sequence system
  • Self-diagonostic test by one touch for "CLR" key
  • Alarm befor Tripping by over current
  • History,Latest 8 trip events
  • To have stable state under the noise environment :connection cable with line noise filter between indication meter and converter
  • Convenient installation into existed meter hole:65Φ hole or rectangular hole
Technical Specification
  • Current rating
    • 70 Type : 0.2A∼70A / 0.5A~6A with external CT
    • 03 Type : 0.2A ∼6A, Only for 5SM Type
    • External CT : 1A ∼ 3000A
  • Operation Time
    • Starting trip delay time(dt) : 1 ~ 300sec /Definite T-I
    • Over current trip delay time(ot)
      • definite T-I:0.1~60sec
      • Inverse :5~30 Class
      • 0.08 sec/instant(5SM Type)
    • Under current trip delay time : 0.1~30sec
    • Phase loss trip delay time(PLc) : 1~5sec
    • Reverse phase trip delay time : within 0.5sec
    • Ground fault trip delay time : Edt/0.1~25sec,Eot/0.05,0.1~30sec
    • current unbalance trip delay time : 8sec
    • locked rotor trip delay time : dt+0.1sec
  • Allowable tollerance
    • Current : C≤2A : 0.2A, C>2A : ±5%
    • Time : t≤2sec : ±0.2sec, t>2sec : ±10%
    • Control power : 24VDC (Optional Type)
  • Trip output
    • Main : 97-98 : 1a(1-SPST),3A/Resistive
    • C1-M : 1a (1-SPST),3A/Resistive
    • Aux:07-08 : 1a(1-SPST),3A/Resistive(possible to output one of,AlEc/AL/uc/Shoc/Ec-ta/Ec-tb or SS(5SM type)
  • Application environment
    • Operation : -25℃ ~ +70℃
    • Storage : -40℃ ~ +80℃
    • Relative humidity : 30∼85%, non-condensing
  • Stable operation under frequency variation from Inverter : 20Hz ∼ 400Hz  ,avg ±5% 
  • Screw Torque : Max 0.6N.m
  • Insulation Resistence / IEC-60255-5 : circuit-case, 10Mohm , 500VDC
  • High Voltage Withstand Test : IEC-60255-5
    • circuit-case : AC2000V, 60Hz, 1min
    • contact-contact : AC1000V, 60Hz, 1min
  • Lightning Impulse Voltage Withstand Test : IEC-60255-5
    • Circuit-Ground, Circuit-Circuit : 1.2/50uS, 5KV
    • Control Circuits : 1.2/50uS, 5KV
  • 1MHz Burst Immunity Test / IEC 61000-4-18 : 2.5KV, Positive / Negative under 2sec
  • Electrostatic Discharge : IEC-61000-4-2
    • Air : Level 3, 8KV
    • Contact : Level 13, 6KV
  • Radiated Electromagnetic Field Disturbance / IEC-61000-4-3 : Level 3, 10V/m
  • Electric Fast Transient Burst : IEC-61000-4-4
    • power,relay output : Level 4, 4KV
  • Surge Immunity test : IEC-61000-4-5
    • relay output : 1.2×50uS, 2KV(0°, 90°, 180°, 270°)
  • Conducted Disturbence Test / IEC-61000-4-6 : 10V, Level 3
  • Control Voltage : AC 85V ∼ AC260V,50/60Hz (DC90V ∼ DC370V)
  • Power consumption : 6W Max